Based on the Cibse CP1 2015 / Danish Code of Practice DS 439

https://www.cibse.org/knowledge/knowledge-items/detail?id=a0q200000090MYHAA2

Application

Domestic Hot Water

This standard calculates the diversity based on

  • Number of tapping points

  • Type of the tapping points

  • Total DHW flow

  • Diversified DHW flow

  • Number of dwellings

Diversity formula

With this calculation method, the diversity factor decreases according to the formula (1.19 * N + 18.8 * N^0.5 + 17.6) / (37.5*N), in which N is the number of dwellings.

The diversified flow rate for one dwelling is calculated based on the default power 37,5 kW as mentioned in the DS 439 (CIBSE CP1 2015).

image-20220415-125412.png

Applies diversity

  • inside the dwelling

  • outside the dwelling

Requires recalculation of DHW flows?